Skip to main content

🔗 OPC UA to SQL data logger with python

This script connects to an OPC UA server, reads variable values, and logs them into a MySQL database. The variable names and types are read from a varlist.txt file.

Prerequisites​

  • Python 3.x
  • opcua library
  • mysql-connector-python library
  • MySQL server

Installation​

  1. Install the required Python libraries:

    pip install opcua mysql-connector-python
  2. Ensure you have a MySQL server running and accessible.

Configuration​

  1. OPC UA Server URL: Update the OPC_UA_SERVER variable with the URL of your OPC UA server.

    OPC_UA_SERVER = "opc.tcp://192.168.30.108:4840"
  2. Variable Namespace: Update the VAR_NAMESPACE variable with the namespace of your OPC UA server.

    VAR_NAMESPACE = "urn:B&R/pv/"
  3. Polling Interval: Set the polling interval in seconds.

    POLLING_INTERVAL = 60
  4. MySQL Database Connection: Update the MySQL connection details.

    db_connection = mysql.connector.connect(
    host="192.168.1.1",
    user="root",
    password="bur",
    database="data"
    )

Variable list​

Create a varlist.txt file in the same directory as the script. This file should contain the variable names and their types, separated by a semicolon (;). Lines starting with # are treated as comments.

Example:

# VariableName;Type
Temperature;FLOAT
Pressure;FLOAT

Script Workflow​

  1. Read Variable Names and Types: The script reads variable names and types from varlist.txt.
  2. Connect to OPC UA Server: The script connects to the OPC UA server using the provided URL.
  3. List Namespaces: The script lists all namespaces available on the OPC UA server.
  4. Get Namespace Index: The script retrieves the namespace index for the specified namespace.
  5. Create Node IDs and Nodes: The script creates node IDs and nodes for each variable.
  6. Connect to MySQL Database: The script connects to the MySQL database.
  7. Check and Create Columns: The script checks if columns exist in the database table and creates them if they don't.
  8. Read and Log Values: The script reads the values of the nodes cyclically and logs them into the MySQL database.
  9. Error Handling: The script handles any errors that occur during the process.
  10. Disconnect: The script disconnects from the OPC UA server and MySQL database when finished.

Error Handling​

The script includes basic error handling to catch and print exceptions that occur during the connection, reading, and logging processes.